# Modbus Saia Burgess Controls Binding
This binding interfaces the energy meter series ALD1 by Saia Burgess Controls (SBC) via Modbus.
# Supported Things
The following Things are supported:
ald1Unidirectional
: 1-phase 32A one-way energy meter ALD1D5FD00A3A00ald1Bidirectional
: 1-phase 32A two-way energy meter ALD1B5FD00A3A00
# Discovery
This binding does not support discovery.
# Thing Configuration
The following configuration parameter applys to ald1Unidirectional
and ald1Bidirectional
.
Name | Description | Type | Required |
---|---|---|---|
pollInterval | Time between polling the data in ms | Integer | yes |
The Thing needs a Modbus serial slave Bridge to operate.
One of the following serial settings need to be configured in the Bridge:
- 9600 baud, 2 stop bit, no parity
- 9600 baud, 1 stop bit, even parity
- 9600 baud, 1 stop bit, odd parity
# Channels
The following Channels apply to ald1Unidirectional
and ald1Bidirectional
if not stated otherwise.
Name | Type | Description |
---|---|---|
total_energy | Number:Energy | Energy Total |
partial_energy | Number:Energy | Energy Counter Resettable (only unidirectional meter) |
feeding_back_energy | Number:Energy | Energy Feeding Back (only bidirectional meter) |
voltage | Number:ElectricPotential | Effective Voltage |
current | Number:ElectricCurrent | Effective Current |
active_power | Number:Power | Effective Active Power (negative numbers mean feeding back) |
reactive_power | Number:Power | Effective Reactive Power (negative numbers mean feeding back) |
power_factor | Number:Dimensionless | Power Factor |
# Full Example
# .items
Number:Energy ALD1_Total_Energy "[%.2f %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:total_energy"}
Number:Energy ALD1_Feeding_Back_Energy "[%.2f %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:feeding_back_energy"}
Number:ElectricPotential ALD1_Voltage "[%d %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:voltage"}
Number:ElectricCurrent ALD1_Current "[%.1f %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:current"}
Number:Power ALD1_Active_Power "[%.2f %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:active_power"}
Number:Power ALD1_Reactive_Power "[%.2f %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:reactive_power"}
Number:Dimensionless ALD1_Power_Factor "[%.2f]" {channel="modbus:ald1Bidirectional:8b6e85623b:power_factor"}
# .sitemap
sitemap ald1 label="ALD1 Energy Meter"
{
Default item=ALD1_Total_Energy label="Total Energy"
Default item=ALD1_Feeding_Back_Energy label="Feeding Back Energy"
Default item=ALD1_Voltage label="Voltage"
Default item=ALD1_Current label="Current"
Default item=ALD1_Active_Power label="Active Power"
Default item=ALD1_Reactive_Power label="Reactive Power"
Default item=ALD1_Power_Factor label="Power Factor"
}
Caught a mistake or want to contribute to the documentation? Edit this page on GitHub (opens new window)