# Warmup Binding
This binding integrates the Warmup 4iE Thermostat https://www.warmup.co.uk/thermostats/smart/4ie-underfloor-heating (opens new window), via the API at https://my.warmup.com/ (opens new window).
Any Warmup 4iE device(s) must be registered at https://my.warmup.com/ (opens new window) prior to usage.
This API is not known to be documented publicly. The binding api implementation has been derived from the implementations at https://github.com/alyc100/SmartThingsPublic/blob/master/devicetypes/alyc100/warmup-4ie.src/warmup-4ie.groovy (opens new window) and https://github.com/alex-0103/warmup4IE/blob/master/warmup4ie/warmup4ie.py (opens new window), and enhanced by inspecting the GraphQL endpoint.
# Supported Things
The Warmup binding supports the following thing types:
Bridge | Label | Description |
---|---|---|
my-warmup | My Warmup Account | The account credentials for my.warmup.com (opens new window) which acts as an API to the Warmup device(s) |
Thing | Label | Description |
---|---|---|
room | Room | A room containing an individual Warmup 4iE device which is a WiFi connected device which controls a heating circuit. |
# Room
The device is optimised for controlling underfloor heating (electric or hydronic), although it can also control central heating circuits. The device reports the temperature from one of two thermostats, either a floor temperature probe or the air temperature at the device. The separate temperatures do not appear to be reported through the API. It appears to be possible to configure two devices in a primary / secondary configuration, but it is not clear how this might be represented by the API and hasn't been implemented.
# Discovery
Once credentials are successfully added to the bridge, any rooms (devices) detected will be added as things to the inbox.
# Thing Configuration
# My Warmup Account
config parameter | type | description | required | default |
---|---|---|---|---|
username | String | Username for my.warmup.com (opens new window) | true | |
password | String | Password for my.warmup.com (opens new window) | true | |
refreshInterval | Integer | Interval in seconds between automatic refreshes | true | 300 |
# Room
Rooms are configured automatically with a Serial Number on discovery, or can be added manually using the "Device Number" from the device, excluding the last 3 characters. The only supported temperature change is an override, through a default duration configured on the thing. This defaults to 60 minutes.
config parameter | type | description | required | default |
---|---|---|---|---|
serialNumber | String | Device Serial Number, excluding last 3 characters | true | |
overrideDuration | Integer | Duration in minutes of override when target temperature is changed | true | 60 |
# Channels
channel | type | description | read only |
---|---|---|---|
currentTemperature | Number:Temperature | Currently reported temperature | true |
targetTemperature | Number:Temperature | Target temperature | false |
overrideRemaining | Number:Time | Duration remaining of the configured override | true |
runMode | String | Current operating mode of the thermostat, options listed below | true |
frostProtectionMode | Switch | Toggles between the "Frost Protection" run mode and the previously configured "active" run mode (known options are either Fixed or Schedule) | false |
# Run Mode Statuses
These run mode statuses are defined for the API. The descriptions are based on inspection of the device behaviour and are not sourced from documentation.
api value | ui name | description |
---|---|---|
not_set | Not Set | Unknown |
off | Off | Device turned off |
schedule | Schedule | Device target temperature running to a programmed schedule |
override | Override | Target temperature overridden for the remaining duration in overrideRemaining |
fixed | Fixed | Device target temperature set to a constant fixed value |
anti_frost | Frost Protection | Device target temperature set to 7°C |
holiday | Holiday | Device target temperature set to a constant fixed value for duration of holiday |
fil_pilote | Fil Pilote | Unknown |
gradual | Gradual | Unknown |
relay | Relay | Unknown |
previous | Previous | Unknown |
# Full Example
# .things file
Bridge warmup:my-warmup:MyWarmup [ username="[email protected]", password="test", refreshInterval=300 ]
{
room bathroom "Home - Bathroom" [ serialNumber="AABBCCDDEEFF", overrideDuration=60 ]
}
# .items file
Number:Temperature bathroom_temperature "Temperature [%.1f °C]" <temperature> (GF_Bathroom, Temperature) ["Temperature"] {channel="warmup:room:MyWarmup:bathroom:currentTemperature"}
Number:Temperature bathroom_setpoint "Set Point [%.1f °C]" <temperature> (GF_Bathroom) ["Set Point"] {channel="warmup:room:MyWarmup:bathroom:targetTemperature"}
Number:Time bathroom_overrideRemaining "Override Remaining [%d minutes]" (GF_Bathroom) {channel="warmup:room:MyWarmup:bathroom:overrideRemaining"}
String bathroom_runMode "Run Mode [%s]" (GF_Bathroom) {channel="warmup:room:MyWarmup:bathroom:runMode"}
Switch bathroom_frostProtection "Frost Protection Mode" (GF_Bathroom) {channel="warmup:room:MyWarmup:bathroom:frostProtectionMode"}
# Sitemap
Text label="Bathroom" {
Text item=bathroom_temperature
Setpoint item=bathroom_setpoint step=0.5
Text item=bathroom_overrideRemaining
Text item=bathroom_runMode
Switch item=bathroom_frostProtection
}